Riser tube at rolled connection at drum in Power
Boiler
Observation : Short longitudinal cracks with numerous
parallel cracks
Cause : Long Term Overheat/ CreepRemarks : Caused when steam flow is blocked or partially
restricted or when the heating capacity of the tube exceeds